Short Circuit Analysis for US Industrial Facilities

A short circuit study answers one question with two consequences. How much fault current is available at each point, and is the installed equipment rated to interrupt it. Equipment that is under-rated does not trip a fault, it fails into it. In the US that calculation starts with available fault current from your serving utility, and an assumed figure makes every result unverifiable.

Free Consultation
NFPA 70EIEEE 1584OSHA CompliantNEC Standards

What a Short Circuit Study Establishes

Fault current decides equipment adequacy, protection settings and arc flash energy. All three inherit the same source number.

What We Deliver

Available fault current per location

Three-phase and single line to ground fault current at each bus, derived from utility data and the network between it and the point in question. ANSI and IEEE C37 methods are the usual basis for equipment duty.

WHAT GOES WRONG

Where Short Circuit Studies Fail

The arithmetic is well established. The failures are in the inputs, and the consequence of a wrong input is equipment rated for a fault it will not actually have to interrupt.

  • Utility available fault current assumed rather than obtained in writing.
  • Motor contribution to fault current omitted on motor-heavy plant.
  • Conductor impedance estimated rather than calculated from actual lengths.
  • Equipment ratings taken from drawings rather than nameplates.
  • Study not repeated after a service upgrade or utility reinforcement.
  • Results used for arc flash labelling without the coordination study in between.
Contact Us
Switchgear inspection for short circuit analysis at a US facility
Short circuit analysis report from Carelabs

THE OUTCOMES

What the Report Contains

The report names the utility figure and where it came from on its first page, because every number after that derives from it and an unsourced fault current cannot be defended to an AHJ.

  1. 1Utility available fault current with written source
  2. 2Fault current per bus, three-phase and line to ground
  3. 3Equipment interrupting adequacy, device by device
  4. 4Any under-rated equipment identified explicitly
  5. 5Motor contribution where it is material
  6. 6Assumptions, impedance data and study date
Reach Out

How We Run a US Short Circuit Study

01

Obtain utility fault data

Request available fault current and source impedance in writing from the serving utility, since this is the figure every later result derives from.

02

Verify the network

Confirm the single line against the installation, recording conductor sizes and lengths and reading equipment ratings from nameplates rather than drawings.

03

Include motor contribution

Account for motor contribution to fault current where the plant is motor-heavy, since omitting it understates duty at the buses that matter most.

04

Calculate and compare

Fault current at each location, compared against the interrupting rating of the device installed there, with any inadequacy called out.

05

Report and carry forward

Results documented with their source data, and handed to the coordination study rather than straight to arc flash labelling.

Industries We Empower

Oil & Gas

Upstream, midstream, and downstream facilities

Healthcare

Hospitals, clinics, and medical campuses

Data Centers

Tier I through Tier IV facilities

Manufacturing

Production lines and industrial plants

Utilities

Generation, transmission, and distribution

Commercial Real Estate

Office buildings and retail complexes

Education

Universities, schools, and research labs

Government

Federal, state, and municipal facilities

Related Resources

Load flow analysis insights

Engineering

Key Insights from Load Flow Analysis

How load flow and short circuit analysis work together for complete system assessment.

Read More
Arc flash hazard analysis

Safety

Arc Flash Hazard Analysis Importance

Why accurate fault current data is critical for arc flash calculations.

Read More
Arc flash study compliance

Compliance

Arc Flash Study: A Necessity

How short circuit analysis feeds into your NFPA 70E compliance program.

Read More

Frequently Asked Questions

Because equipment that is not rated for the fault current available at its location does not interrupt the fault, it fails into it. The study establishes available fault current at each point and compares it against the interrupting rating of the device installed there. Anything under-rated is a safety defect rather than a documentation gap.
From your serving utility, in writing. It depends on the upstream network, not just on your service transformer, so it cannot be reliably derived from the equipment on site. Utilities also change it when they reinforce the network, usually without notifying connected customers, which is what gives a study its shelf life.
Yes, and on motor-heavy plant it is material. Running motors contribute to fault current for the first few cycles, raising the duty at nearby buses above what the utility source alone would produce. Omitting motor contribution understates fault duty precisely where the largest equipment sits.
Not defensibly. Incident energy depends on both fault current and how long the fault persists, and clearing time comes from the protection coordination study. Skipping coordination means clearing times are assumed, and an assumed clearing time produces a PPE category that cannot be justified if an inspector asks for the basis.

Confirm Your Equipment Can Interrupt What It Would Actually See