Skip to content

IEEE 1584 · Engineering

Load Flow Analysis For A Resilient Power System

Load flow analysis solves the steady-state operating condition of your power system — node voltages, branch power flows, real and reactive power, and line losses — for a specified generation and network configuration. For a Singapore facility this means confirming your network can carry required loads during planned outages without exceeding rated capacity, and identifying where reactive power compensation and transformer tap settings should sit for efficient operation. Carelabs performs the study in ETAP, modelling your network as nodes connected by impedances and solving it iteratively, and delivers findings aligned with SS 638.

Free Consultation

Capacity inside a building that cannot grow

On a constrained site the answer to more load is rarely more space. It is establishing what the existing risers, transformers and switchrooms can actually carry, and where the first real limit sits.

What We Deliver

Loading on every branch

Transformer, riser and busbar loading is reported against rating for each operating case, which identifies the element that will bind first when load is added rather than the one that is easiest to see.

WHY IT MATTERS

Reinforcing the wrong element

Where space and access are limited, an unnecessary transformer upgrade is expensive in ways that go beyond the equipment. Without a model the upgrade is chosen from the most visible asset rather than the one genuinely binding.

  • Metered demand analysed across a full operating cycle rather than taken from a single peak, since one reading says nothing about diversity.
  • Each switching configuration studied separately, because a network comfortable on the normal arrangement can be constrained on the alternative.
  • Motor starting assessed where chillers and large drives exist, as starting current depresses bus voltage for its duration.
  • Standby generation modelled as its own case, since generator impedance and capacity differ substantially from the supply.
  • Reactive compensation checked for resonance against existing harmonic content before it is recommended rather than after installation.
Contact Us

DELIVERABLES

What you receive

Issued against SS 638 with the load basis and modelling assumptions stated so conclusions can be audited.

  1. 1Measured demand profile with diversity quantified
  2. 2Bus voltage table per scenario with deviation from nominal against the applicable limit
  3. 3Branch loading summary naming every element above rating and the margin on those approaching it
  4. 4Spare capacity in kVA at the constraining element, for fit-out and expansion decisions
  5. 5The calibrated ETAP model, so the next tenant or plant change is a re-run
Reach Out

How the study runs

01

Frame the decision

We establish what must be settled: a fit-out, a plant replacement, or how much load can still be added before reinforcement becomes unavoidable.

02

Establish real demand

Metered data is collected across a representative cycle and reconciled against connected load, since the gap between them is usually the finding.

03

Build the model

Transformers, risers and busbars are modelled in ETAP from verified data, with impedances taken from certificates where those exist.

04

Solve the scenarios

Present operation, maximum demand, alternative switching and planned load are each solved as separate cases.

05

Name the constraint

The first binding element is identified per case with its remaining margin, which is the number a capacity decision actually requires.

06

Options and handover

Reinforcement, reconfiguration and compensation options are presented with the constraint each relieves, and the model is handed over.

Frequently asked questions

Frequently yes. The supply is often not the binding element; a riser, a sub-main or a switching arrangement usually limits the site first. Load flow identifies which, and relieving an internal constraint is normally far cheaper and less disruptive than increasing the intake capacity.
Diversity is the central question. Summing every tenant's connected load produces a figure no building ever reaches, while assuming heavy diversity risks a constraint appearing at peak. Metered data across a full cycle establishes the real position, which is what makes a fit-out approval defensible.
Where chillers are large relative to the supply, yes. Starting current depresses bus voltage for the duration of the start, and a network comfortable in steady state can drop out contactors or trip sensitive equipment during it. That transient is modelled rather than assumed acceptable.
The same verified network supports short circuit, arc flash, protection coordination and harmonic work. Capturing and validating the network is the largest part of the cost of any of those, so retaining the model means the next question is answered in days rather than by repeating the survey.

Schedule Your Load Flow Analysis For A Resilient Power System

Tell us about your project.